The Australian Standard AS/NZS 2589 Gypsum linings – Application and finishing specifies different spacing requirements, conventional spacing and 1/3 spacing, for the installation of fasteners and adhesives in gypsum board ceilings based on specific needs and conditions.
Conventional Spacing is typically used under normal conditions where extra support is not crucial. It is generally adequate for standard residential buildings and internal areas without unusual load or significant environmental stressors. This standard spacing is sufficient in environments less affected by moisture, high winds, or structural movements, and where the ceiling does not support heavy fixtures or additional loads.
1/3 Spacing reduces the distance between fasteners and adhesives, thus increasing the number of fasteners used, providing greater support and stability. The 1/3 spacing is recommended for areas that may be subject to higher loads or where additional factors such as wind, vibration, moisture, or thermal expansion could impact the integrity of the ceiling.

Unfortunately, this standard does not explicitly explain where the 1/3 spacing should be used. However, it clearly specifies that the installation of plasterboard linings must meet the requirements of Serviceability limit state. According to AS/NZS 2589 section 3.2.1: “Serviceability limit state – Consideration shall be made of the effects on installed gypsum linings resulting from self weight, humidity, imposed actions and internal and external environmental conditions. Notes: Sag in ceiling linings can occur over time as a result of self-weight, humidity, imposed actions and internal and external environmental conditions. Typical imposed actions include light fittings, fans, insulation and other services that might be fully or partially supported by the gypsum linings.”
Particularly for ceilings in garages, carports, verandahs, and alfresco areas, which are subject to more extreme conditions and loads, special attention is necessary for their fixing and detailing. Factors such as wind loads, condensation, roller door vibrations, and exposure to atmospheric variations (e.g., humidity, temperature) necessitate the use of 1/3 spacing.

Therefore, in MFS’s view, ceilings in these areas should use the 1/3 spacing in Table 3 of AS/NZS 2589 to meet the serviceability limit state requirement of clause 3.2.1.
References
- Standards Australia, AS/NZS 2589 Gypsum linings, clauses 3.2.1 and 7.6.3.6, Table 3.
- Building Commission (WA), Industry Bulletin 085, Plasterboard ceiling failures (updated May 2017). wa.gov.au